EasyManuals Logo
Home>Lennox>Air Conditioner>MMDA048S4-*P

Lennox MMDA048S4-*P User Manual

Lennox MMDA048S4-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #139 background imageLoading...
Page #139 background image
139
Error Code: F3
Description: Compressordischargetemperaturesensorerror
General Note: Whenthecompressordischargetemperature(T5)ismorethan115°Cfor10seconds,thecompressorwillstopandrestart
tillT5islessthan90°C.
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan115°C?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringcon-
nection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Other manuals for Lennox MMDA048S4-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MMDA048S4-*P and is the answer not in the manual?

Lennox MMDA048S4-*P Specifications

General IconGeneral
BrandLennox
ModelMMDA048S4-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals