EasyManuals Logo

Lennox MPA009S4S User Manual

Lennox MPA009S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #109 background imageLoading...
Page #109 background image
109
Error Code: E5
Description: Highorlowvoltageprotection
General Note: Anabnormalvoltageriseordropisdetectedbycheckingthespeciedvoltagedetectioncircuit.
Voltage protection
Checkthevoltageofoutdoorunitpower
supply,thevoltagebetween
L1andL2rangemin.187~253VACmax.
Yes
CheckwhetherthevoltageofIPMboard
PandNisnormal?277-356VDCfor
18-30KBtu/h;277-410VDCfor36KBtu/h.
No
Replacebridgerectiers,andthencheck
whetherthesystemoperatesnormally.
(Onlyfor4-zoneMPA036&MLA036
units)
No
ReplaceIPMboard,andthencheck
for normal unit operation.
No
Replaceoutdoormainboard.
Problem Solved.
Yes
Yes
Checktheprimarypowersupply.
No