EasyManuals Logo

Lennox MPA009S4S User Manual

Lennox MPA009S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
119
Error Code: P2
Description: Lowpressureswitchopen.
General Note: Ifthesamplingvoltageisnot5V,theLEDwilldisplaythefailure.
LowPressureConnection
Isthewiringbetweenthelowpressureswitchand
main control board is connected properly.
Yes
Isthelowpressureprotectorbroken?
Method:Disconnecttheplug.Measuretheresistance
ofthelowpressureprotector,iftheprotectorisnormal
thevalueis0.
Yes
Connect it properly..
No
Replacelowpressureprotector.
No
Checkwhethertheoutdoorambienttemperatureisto
low.
No
Stoptheunit.
Yes
Checkwhetherthehighpressurevalveisopened.
Yes
Fullyopenthehighpressurevalve.
No
Checkiftheindoorfanrunsproperlyincoolingmode.
Refertothesolutionoffanspeedmal-
function(E8).Findoutthecausecorrect
it.
No
Yes
Replaceoutdoormainboard.
No
Refrigerantisnotenough.Addtherefrigerant.

Table of Contents