TPA*H4 SERIES
Table 5. Indoor Unit Match ups and Target Subcooling Values
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)(+1ºF)
*Add
charge
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)(+1ºF)
*Add
charge
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)(+1ºF)
*Add
charge
TPA*H4036 lb oz 14HPX/XP14/TPA*H4042 (Continued) lb oz 14HPX/XP14/TPA*H4048 (Continued) lb oz
C33−44C 13 6 0 0 CBX32M−048 12 6 0 7 CH33−62D 10 7 1 14
CBX26UH−036 26 5 0 0 CBX32MV−048 12 6 0 8 CR33−50/60C 35 5 0 0
CBX26UH−037 25 4 1 9 CBX40UHV−042, −048 12 6 0 8 CR33−60D 37 6 0 0
CBX27UH−036 13 6 0 3 CH33−43 12 6 0 7 CX34−62C, −62D 10 7 1 7
CBX32M−036 13 6 0 2 CH33−62D 12 6 0 10 CX34−49C 11 8 0 14
CBX32M−042 13 6 0 3 CH33−50/60C 12 6 0 7 CX34−60D 11 8 0 0
CBX32MV−036 13 6 0 3 CH33−60D 12 6 0 4 14HPX/XP14/TPA*H4060 lb oz
CBX32MV−048 11 8 2 5 CR33−50/60C,−60D 26 6 0 4 CBX26UH−048 12 7 1 0
CBX40UHV−036 13 6 0 3 CX34−62C, −62D 12 6 0 9 CBX26UH−060 14 4 0 0
CBX40UHV−042, −048 11 8 2 5 CX34−49C 12 6 0 7 CBX27UH−060 12 5 0 0
CH33−50/60C 11 8 2 5 CX34−60D 12 6 0 4 CBX32M−048, −060 12 5 0 0
CH33−44B 13 6 1 7 14HPX/XP14/TPA*H4048 lb oz CBX32MV−048, −060 12 5 0 0
CH33−48B 13 6 1 8 CBX26UH−048 8 7 1 9 CBX40UHV−048, −060 12 5 0 0
CR33−50/60C 25 4 1 15 CBX27UH−048 11 8 1 2 CBX32MV−068 12 7 1 0
CR33−48B/C 25 5 0 9 CBX32M−048, −060 11 8 1 2 CH23−68 12 5 0 0
CX34−49C 13 6 2 4 CBX32MV−048 25 8 0 0 CH33−50/60C 12 5 0 0
CX34−43B/C, −50/60C 13 6 1 8 CBX32MV−060 11 8 1 2 CH33−62D 12 5 0 0
CX34−38A/B S/N# 6007 and
after
6 6 0 0 CBX40UHV−048 25 8 0 0 CX34−62C, −62D 12 7 1 0
CX34−38A/B before S/N#
6007
13 6 0 0 CBX40UHV−060 11 8 1 2
*Add charge = Extra matchup amount required in addition to
charge indicated on Heat Pump nameplate (remember to also
add any charge required for line set differences from 15 feet).
SN indicates serial number.
TPA*H4042 lb oz CBX32MV−068 10 7 1 12
CH23−68 20 9 0 13 CH23−68 20 9 2 9
CBX26UH−042 27 6 0 0 CH33−50/60C 11 8 1 1
CBX27UH−042 12 6 0 8 CH33−60D 11 8 0 0
Table 6. CTXV Normal Operating Pressures Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Use table 6 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer
to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in
installations. Significant differences could mean that the system is not properly charged or that a problem exists with some
component in the system.
5F (5C)**
TPA*H4−036 TPA*H4−042 TPA*H4−048 TPA*H4−060
Liquid/ Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
HEATING
60 (15) 350 / 134 373 / 139 355 / 130 351 / 117
50 (10) 331 / 117 363 / 117 336 / 113 333 / 105
40 (4) 313 / 97 348 / 97 315 / 88 316 / 88
30 (−1) 298 / 83 336 / 74 296 / 72 308 / 70
20 (−7) 284 / 66 322 / 64 286 / 64 300 / 61
COOLING
65 (18) 220 / 138 223 / 125 231 / 136 243 / 136
70 (21) 236 / 140 241 / 130 248 / 139 263 / 137
75 (24) 256 / 141 261 / 134 271 / 140 282 / 138
80 (27) 276 / 142 282 / 138 291 / 142 306 / 139
85 (29) 298 / 143 302 / 139 312 / 143 327 / 140
90 (32) 321 / 144 326 / 140 335 / 144 351 / 141
95 (35) 344 / 144 349 / 141 359 / 145 376 / 142
100 (38) 369 / 146 374 / 142 384 / 146 401 / 143
105 (41) 394 / 147 399 / 143 411 / 148 426 / 145
110 (38) 421 / 148 428 / 145 439 / 149 452 / 146
115 (45) 449 / 149 455 / 146 468 / 150 484 / 148
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil (outdoor ambient temperature).