38
SETTINGS
INSTALLATION
INFO
TOTAL CHARGE 999 LBS Field input
COMMISSION 01/20/19 Field input
DIP SWITCH
READING
Refer to "DIP SWITCH READING" table
FUNCTION
SETTINGS
INDOOR TEMP
UNIT
F
Command, can change all the indoor unit
temperature unit to C/F
T4 PRIORITY 70°F Field setting, options:50F/60F/70F
COMP. LOCKOUT -14°F
Ambient temperature for compressor
lockout setting in heating mode.
T2 TARGET 115°F
Field setting, options: 104/108/111/115(DEF
AULT)/119/122F
T2B TARGET 50°F
Field setting, options:
43/47/50(DEFAULT)/53/56/59F
DEMAND
CONTROL
100%
Field setting, options:
100%/90%/80%/70%/60%/50%/40%
VIP ADDRESS 63
Field setting, options: 0~63, OXFF - no VIP
indoor
SNOW MODE NONE Field setting, options: NONE/HEAVY/LIGHT
CHANGE
PASSWORD
Default password is 0000
SERVICE
SERVICE MODE
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
TEST OPERATION
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
COOLING TEST
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
HEATING TEST
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
MANUAL DEFROST
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
REFRIGERANT
RECYCLE MODE
RECYCLE TO
ODU
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
RECYCLE TO
IDU
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
RECYCLE TO
PIPING
Command, select "YES" to enter and "NO"
to exit and press "Enter" to conrm the
command.
ASSIGN IDU
ADDRESS
Command, automatically assign addresses
to the indoor units in the system.
ECO MODE
Field setting.
CANCEL LVM
E-STOP
Command, clear the emergency stop status
from LVM in case LVM is broken.
CLEAR IDU
ADDRESS
Command, clear all indoor unit addresses
in the system.
FACTORY
SETTINGS
Command