EasyManuals Logo

Lennox ZGB Series User Manual

Lennox ZGB Series
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image

BURNER BOX ASSEMBLY
S18
Combustion Air
Prove Switch
Gas Valve
Gas
Manifold
Vent Connector
B6
Combustion
Air Inducer
Combustion Air
Prove Switch Tubing
FIGURE 11
6-Combustion Air Inducer B6
Combustion air inducers provide air to the corresponding
burners while clearing the combustion chamber of ex-
haust gases. The inducer begins operating immediately
upon receiving a thermostat demand and is de-energized

       
     
       
protection. Inducers are supplied by various manufactur-

electrical ratings can be found on the unit rating plate.
         -
        
the combustion air inducer to vent exhaust gases from

-
        

the combustion air prove switch is closed and the delay is

-
       
sensed or at the end of the eight second trial for ignition.
        -
       
start the inducer in high speed for second-stage heat


All combustion air inducer motors are sealed and cannot
be oiled. The inducer cannot be adjusted but can be re-
moved from the vestibule to clean the wheel.
7-Combustion Air Motor Capacitor C3
The combustion air inducer motors in all ZGB units require
run capacitors. Capacitor C3 is connected to combustion
-
bustion air motor nameplate.
8-Gas Valves GV1
Units are equipped with a single or two stage gas valve.
-
gized by the ignition control simultaneously with the spark

second stage operator is energized directly from A3. A
󰀨
󰀨󰀨

󰀨


shows factory gas valve regulation pressures.
TABLE 7

Natural 
 High  High
1.7  3.5    
9-Spark Electrode (Ignitor) Figure 12
An electrode assembly is used for ignition spark. The elec-
trode is mounted through holes under the burner located
farthest to the right. The electrode tip protrudes into the
-
sembly is fastened to burner supports and can be removed
for service without removing any part of the burners.


burner to burner until all are lit.
The spark electrode is connected to the ignition control by

female quick connects on both ends of the wire.
NOTE - If electrode wire must be replaced, wire and sup-
pression must be same type cable. See www.davenet for
replacement.
The spark electrode assembly can be removed for inspec-
tion by removing the screw securing the electrode assem-
bly and sliding it out of unit.

and gapped correctly. Spark gap may be checked with
appropriately sized twist drills or feeler gauges. Discon-
nect power to the unit and remove electrode assembly.



Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ZGB Series and is the answer not in the manual?

Lennox ZGB Series Specifications

General IconGeneral
BrandLennox
ModelZGB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals