EasyManuals Logo

Lennox ZGB Series User Manual

Lennox ZGB Series
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image

A6 ENTHALPY CONTROLLER
A
B
C
D
Open
Min
Pos
FREE COOLING SETPOINT;
A=Completely counterclockwise
D=Completely clockwise
OUTDOOR AIR
SUITABLE LED
Free
Cool
DCV
EXH
EXH
Set
2V 10V
DCV
Max
2V 10V
DCV
Set
2V 10V
IAQ SETPOINT
IAQ READING IS
ABOVE SETPOINT
MUM POSITION
IAQ MAXIMUM
POSITION
(set higher than
minimum position)
FIGURE 27
Free Cooling Setpoint
Outdoor air is considered suitable when temperature and
humidity are less than the free cooling setpoints shown






󰀨
      

TABLE 13
ENTHALPY CONTROL SETPOINTS
Control Setting 
A 
B 
C 
D 
Damper Minimum Position
1 - Set thermostat to occupied mode if the feature is

OC are connected if using a thermostat which does
not have the feature.
2 - 
desired fresh air percentage.
Note - Damper minimum position can be set lower
than traditional minimum air requirements when
an IAQ sensor is specied. Dampers will open to
DCV MAX setting (if CO2 is above setpoint) to meet
traditional ventilation requirements.
3 - Measure outdoor air temperature. Mark the point


 Measure return air temperature. Mark that point on


5 -       
temperature. Mark that point on the top line of chart

 Draw a straight line between points A and B.
7 - Draw a vertical line through point C.
 Draw a horizontal line where the two lines meet.

   
MIN POS SET potentiometer higher. If fresh air


until calculation reads desired fresh air percentage.
DCV Set and Max Settings
Adjust settings when an optional IAQ sensor is installed.
The DCV SET potentiometer is factory-set at approxi-



DCV SET potentiometer to the approximate setting speci-

The DCV MAX potentiometer is factory-set at approxi-
-
ers will open approximately half way when CO2 rises
above setpoint. Adjust the DCV MAX potentiometer to the
      

Note - DCV Max must be set higher than economizer min-
imum position setting for proper demand control ventila-
tion.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ZGB Series and is the answer not in the manual?

Lennox ZGB Series Specifications

General IconGeneral
BrandLennox
ModelZGB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals