Ambient temperature management
The server is supported in the following environment:
Air temperature:
Operating:
ASHRAE class H1: 5–25°C (41–77°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient
temperature value decreases by 1°C (1.8°F) with every 500 m (1640 ft) of altitude increase.
ASHRAE class A2: 10–35°C (50–95°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient
temperature value decreases by 1°C (1.8°F) with every 300 m (984 ft) of altitude increase.
ASHRAE class A3: 5–40°C (41–104°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient
temperature value decreases by 1°C (1.8°F) with every 175 m (574 ft) of altitude increase.
ASHRAE class A4: 5–45°C (41–113°F); when the altitude exceeds 900 m (2953 ft), the maximum ambient
temperature value decreases by 1°C (1.8°F) with every 125 m (410 ft) of altitude increase.
Server off: 5–45°C (41–113°F)
Shipping or storage: -40–60°C (-40–140°F)
Maximum altitude: 3050 m (10 000 ft)
Relative humidity (non-condensing):
Operating:
ASHRAE Class H1: 8%–80%, maximum dew point: 17°C (62.6°F)
ASHRAE Class A2: 8%–80%, maximum dew point: 21°C (70°F)
ASHRAE Class A3: 8%–85%, maximum dew point: 24°C (75°F)
ASHRAE Class A4: 8%–90%, maximum dew point: 24°C (75°F)
Shipment or storage: 8%–90%
Particulate contamination
Attention: Airborne particulates and reactive gases acting alone or in combination with other environmental factors
such as humidity or temperature might pose a risk to the server. For information about the limits for particulates and
gases, see
“Particulate contamination” on page 11.