Service Action:
Complete the following steps:
1. Check the log for a separate error related to an associated PCIe device and resolve that error.
2. Perform PD on PCIe error by moving the adapter to a different slot. If error follows the adapter, replace it.
3. Inspect processor socket. If socket is damaged, replace the system board.
4. If problem persists, escalate to next level support.
FQXSFMA0001I: DIMM [arg1] Disable has been recovered. [arg2]
Severity: Info
User Action:
Information only; no action is required.
Service Action:
Information only; no action is required.
FQXSFMA0001M: DIMM [arg1] has been disabled due to an error detected during POST. [arg2]
Severity: Error
User Action:
Complete the following steps:
1. Reseat the affected DIMM (Note: The event Log might contain a recent FQXSFMA0011I event
denoting detected change in DIMM population that could be related to this problem.)
2. Boot to F1 setup and enable the DIMM (For AMD, do not need to enable DIMM in Setup). Reboot the
system.
3. Update UEFI firmware to the latest version.
4. If the problem persists, collect Service Data logs.
5. Contact Lenovo Support.
Service Action:
Complete the following steps:
1. Verify PD steps.
2. Replace the failing DIMM identified by LightPath and/or event log entry if -V20 is NOT appended to the DIMM
Serial Number in the FFDC event log.
3. If problem persists, replace system board.
4. If problem persists, escalate to next level support.
FQXSFMA0002I: The uncorrectable memory error state has been cleared.
Severity: Info
User Action:
Information only; no action is required.
Service Action:
Information only; no action is required.
Chapter 3. UEFI events 201