10
ENGLISH
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
P419
CANopen status 0 Not initialized Read-only
Note: RPDOs and TPDOs are only
active in operational state (P419 = 5)
1 Initializing
2 Stopped
3 Pre-operational
4 reserved
5 Operational
P420
Guard time 0 0 {ms} 65535 P420 x P421 = node life time
If RTR frame with ID = 0x700 + Node
ID (P410) is not received during the
node life time, the controller will react
according to P422
If heart beat message is enabled, the
guard function is disabled
P422 is only active when drive is
in Network Control mode (n.xxx)
and at least one RTR frame with
ID=0x700+NODE ID has been received.
P421
Life time factor 0 0 255
P422
Guard time event
reaction
0 0 Not active
1 STOP (see
P111)
2 Quick stop
3 Inhibit
4 Trip fault
F.nF1
P423
Error behavior 1
0 transition to pre-operational
(only if current state is operational)
Specifies action taken by the drive when it
encounters a communication error
(ex. Node guarding event or Bus Off)
1 No state change
2 transition to stopped
P425
Message
monitoring time
0 0 {ms} 65535 P425 and P426 can be used to monitor
all valid messages (e.g. SDO, SYNC,
PDO...)
P425 = 0 or P426 = 0 disables message
monitoring function
P426 is only active when drive is in
Network Control Mode (n.xxx)
P426
Message
monitoring time
out reaction
0 0 Not active
1 STOP (see P111)
2 Quick stop
3 Inhibit
4 Trip fault
F.nF2
P427
Monitoring time-
out status
Bits: Read-only
Indicates cause of
F.nt (trip fault,
inhibit, quick stop, or Stop) depending
on the settings of P422, P426, P445,
P455
0 Guard time time-out
1 No valid message received
2 RPD01 time-out
3 RPD02 time-out
4 reserved
5 reserved
6 reserved
7 reserved