17
L
Assembly
Make the contact from controller, RFI filter, and mains chokes to
the grounded mounting plate with as large a surface as
possible. Zinc-coated mounting plates allow long-lasting
contacts. For painted plates the paint of the mounting plates
must be removed in all cases.
If you use several mounting plates:
Make a conductive connection of the mounting plates with as
large a surface as possible (e.g. using copper bands).
Connect the screen of the armature and field cable to the
mounting plate with as large a surface as possible:
Recommendation: Make the large-surface connection of the
screens to the mounting plate with earthing clamps on bare
metal mounting surfaces.
If there are contactors, motor protection switches, or terminals
in the armature cable:
Contact of the screens of the connected cables to each other
and to the mounting plate with as large a surface as
possible.
In the terminal box, connect the screen of the motor to PE:
Metal cable glands at the motor terminal box ensure a large-
surface connection of the screen to the motor housing.
If the total length of the mains cable between RFI filter and
mains chokes and controller exceeds 200 mm:
Screen mains cables
Connect the screen of the mains cables to the mounting
plate with as large a surface as possible.
Connect the screen of the control cables to the mounting plate
with as large a surface as possible.
If you use drive systems with the types 48x in residential areas:
Check the compliance with radio interference voltage level
(EN55022 class B) at the supply location of the operating
area.
Check the permissible radio interference emission
(EN55022 class B) at the supply location of the operating
area.
Please note:
If devices which do not comply with the CE requirement concerning
the noise immunity EN 500882-2 are operated close to the
controllers, an electromagnetic disturbance of these devices by the
controllers is possible.