Appendix
Code table
14−11
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
uSEr
Parameter set
management
−23−
0 0 Ready PAR1 ... PAR4:
Parameter sets of the controller
PAR1 ... PAR4 also contain parameters
for Standard−I/O, Application−I/O,
AS interface or system bus (CAN)
FPAR1:
Module−specific parameter set of the
fieldbus function modules INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
FPAR1 is saved in the function module
7−91
Restorage of
default setting
1 Lenze setting ð PAR1
Restorage of default setting in the selected
parameter set
2 Lenze setting ð PAR2
3 Lenze setting ð PAR3
4 Lenze setting ð PAR4
31 Lenze setting ð FPAR1 Restorage of default setting in the fieldbus
function module
61 Lenze setting ð PAR1 + FPAR1
Restorage of default setting in the selected
parameter set of the controller and the
fieldbus function module
62 Lenze setting ð PAR2 + FPAR1
63 Lenze setting ð PAR3 + FPAR1
64 Lenze setting ð PAR4 + FPAR1
C0002*
uSEr
(cont.)
Parameter set
transfer using the
keypad
Use the keypad to transfer parameter sets
to other controllers.
During transfer the parameters cannot
be accessed via other channels!
Keypad ð Controller
All available parameter sets (PAR1 ... PAR4,
and FPAR1) are overwritten with the
corresponding keypad data
70 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
10
With all other function modules
C0002*
uSEr
(cont.)
Parameter set
transfer using the
keypad
Keypad ð PAR1 (+ FPAR1)
Overwrite selected parameter set and, if
necessary, FPAR1 with the corresponding
keypad data
71 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
11
With all other function modules
Keypad ð PAR2 (+ FPAR1)
72 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
12
With all other function modules
Keypad ð PAR3 (+ FPAR1)
73 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
13
With all other function modules
Keypad ð PAR4 (+ FPAR1)
74 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
14
With all other function modules
Controller ð Keypad
All available parameter sets (PAR1 ... PAR4,
and FPAR1) are copied to the keypad
80 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
20
With all other function modules
Keypad ð Function module
Overwrite the module−specific parameter
set FPAR1 only
40 Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
Function module ð Keypad
Copy the module−specific parameter set
FPAR1 only
50 Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen