Commissioning
Selection of the correct control mode
5−5
L
EDB82MV752 EN 5.2
Application Operating mode
Stand−alone drives
C0014
recommended alternatively
with extremely alternating loads −4− −2−
with heavy start conditions −4− −2−
with speed control (speed feedback) −2− −4−
with high dynamic response (e. g. positioning and infeed drives) −2− −
with torque setpoint −5− −
with torque limitation (power control) −2− −4−
three−phase AC reluctance motors −2− −
three−phase sliding rotor motors −2− −
three−phase motors with fixed frequency−voltage characteristic −2− −
Pump and fan drives with square−law load characteristic −3− −2− / −4−
Group drives
(several motors connected to controller)
identical motors and identical loads −2− −
different motors and/or changing loads −2− −
C0014 = −2−: linear V/f characteristic control
C0014 = −3−: square−law V/f characteristic control
C0014 = −4−: vector control
C0014 = −5−: sensorless torque control