Commissioning
Vector control
5−11
L
EDB82MV752 EN 5.2
11. Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
E82ZBC014
z
y
wx
v
t
u
s
4
00
1
4
000
1
cd
f
PS
p
Para
H/L
SubcodeDispSet
12. Enter the motor data See motor nameplate
A Rated motor speed (C0087)
Lenze setting: 1390 rpm
B Rated motor current (C0088)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
C Rated motor frequency (C0089)
Lenze setting: 50 Hz
D Rated motor voltage (C0090)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
E Motor−cos (C0091)
Lenze setting: Depends on the controller
13. Start the motor parameter identification (C0148) Only when the motor is cold!
A Ensure that the controller is inhibited
misc001
20 28
X3
}
Terminal X3/28 = LOW
B Set C0148 = 1 Press
C Enable the controller
misc002
20
28
X3
Terminal X3/28 = HIGH
The identification starts:
– The segment
is off
– The motor consumes current and makes
a high−pitched" tone.
– The motor does not rotate!
D If the segment becomes active after approx. 30 s,
inhibit the controller once again.
misc001
20 28
X3
}
Terminal X3/28 = LOW
Identification is completed.
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
14. If necessary, change other parameters Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
15. Go to the ALL menu
A Check the fan monitoring setting under code C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
16. Select the setpoint E.g. via potentiometer at
terminals 7, 8, 9
17. Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
18. The drive should now be running. If the drive does not start, press in
addition