Appendix
Code table
14−32
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0351*
System bus baud
rate
0
0 500 kbit/s
Only for the E82ZAFCC system bus
function module on the FIF interface.
Changes will become effective after the
command "reset node"
During operation with 217x
communication modules the baud rate
must be set under C0125.
1 250 kbits/s
2 125 kbits/s
3 50 kbits/s
4 1000 kbits/s (only E82ZAFCC100 function
module)
5 20 kbits/s
C0352*
Configuration of
system bus devices
0
0 slave
Only for the E82ZAFCC system bus
function module on the FIF interface.
Changes will become effective after the
command "reset node"
1 Master
C0353*
Source of system
bus address
0
1
C0350 is the source
C0354 is the source
Only for E82ZAFCC system bus function
module on FIF interface.
Source of the address for system bus
process data channels
1 CAN1 (Sync) 0 Effective for sync control (C0360 = 1)
2 CAN2 0
3 CAN1 (time) 0 Effective for event or time control (C0360 =
0)
C0354*
Selective system
bus address
0 {1} 513 Only for the E82ZAFCC system bus
function module on the FIF interface.
Individual addressing of system bus
process data objects
1 CAN−IN1 (sync) 129
Effective with sync control (C0360 = 1)
2 CAN−OUT1 (sync) 1
3 CAN−IN2 257
4 CAN−OUT2 258
5 CAN−IN1 (time) 385
Effective with event and time control
(C0360 = 0)
6 CAN−OUT1 (time) 386
C0355*
System bus
identifier
0 {1} 2047 Only for the E82ZAFCC system bus
function module on the FIF interface.
Only display
1 CAN−IN1
Identifier of CAN1 with sync control (C0360
= 1)
2 CAN−OUT1
3 CAN−IN2
4 CAN−OUT2
5 CAN−IN1
Identifier of CAN1 with event or time control
(C0360 = 0)
6 CAN−OUT1
C0356*
System bus time
settings
0 {1 ms} 65000 Only for E82ZAFCC system bus function
module on FIF interface.
1 boot up 3000 Required for CAN system without master
2 Cycle time
CAN−OUT2
0 0 = event−controlled process data transfer
> 0 = cyclic process data transfer
3 Cycle time
CAN−OUT1
0 0 and C0360 = 0: event−controlled process
data transfer
> 0 and C0360 = 1: cyclic process data
transfer
4 CAN delay 20 Waiting time until cyclic transmission starts
after boot−up
C0357*
System bus
monitoring times
0 = monitoring
inactive
{1 ms} 65000 Only for E82ZAFCC system bus function
module on FIF interface.
1 CAN−IN1 (Sync) 0 active if C0360 = 1
TRIP CE1 in case of communication fault
2 CAN−IN2 0 TRIP CE2 in case of communication fault
3 CAN−IN1 (time) 0 active if C0360 = 0
TRIP CE3 in case of communication fault