EasyManua.ls Logo

Lenze E94APNE0 4 Series - Page 49

Lenze E94APNE0 4 Series
134 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring the installation backplane
Wiring
Terminal assignment
5
49
EDK94PNE36 DE/EN/FR/ES/IT 2.0
Mains
Terminal X111
(left part)
Labelling Description
L1
L2
L3
Connection of the mains phases L1, L2, L3
Connection for the supply-side PE conductor with M5 ring cable lug
SSP940X111
Terminal X112
(right part)
Labelling Description
L1
L2
L3
Alternative connection at the bottom: mains phases L1, L2, L3
Connection for the supply-side PE conductor with M5 ring cable lug
SSP940X112
Terminal data
Max. conductor cross-section Tightening torque
Screw drive
[mm
2
] [AWG] [Nm] [lb-in]
Device sizes I+II:
flexible
with wire end ferrule
2.5
12 0.5 ... 0.6 4.5 ... 6.2 PZ0
Device size III:
flexible
with wire end ferrule
10 6 1.2 ... 1.5 10.6 ... 13.3 PZ1
External brake resistor
Terminal X112
(left part)
Labelling Description
Rb1
Rb2
External brake resistor
SSP940X112
Terminal data
Max. conductor cross-section Tightening torque
Screw drive
[mm
2
] [AWG] [Nm] [lb-in]
Device sizes I+II:
flexible
with wire end ferrule
2.5
12 0.5 ... 0.6 4.5 ... 6.2 PZ0
Device size III:
flexible
with wire end ferrule
10 6 1.2 ... 1.5 10.6 ... 13.3 PZ1

Table of Contents

Related product manuals