Technical data
General data and operating conditions
4
26
BA_ELx8xx EN 3.0
4 Technical data
4.1 General data and operating conditions
General data
Conformity and approval
Conformity
CE
EN 61000−6−4
EN 61000−6−2
EMC Directive Class A, industrial premises
Approbation
UL UL 508
CSA C22.2
Programmable Controllers (File−No. E236341)
Other
RoHS Products lead−free in accordance with CE Directive
2011/65/EU
Protection of persons and equipment
Safety VDE0805 (EN60950),
VDE0870, UL
Enclosure EN 60529 IP65 (front) / IP20 (back)
UL 508 (NEMA 250) Type 1 enclosure
Class of protection 3
EMC
Noise emission EN 61000−6−4
Class A (industrial premises)
Noise immunity Zone B EN 61000−6−2
Industrial premises
EN 61000−4−2 ESD; severity: 3, i.e.
8 kV in the case of air discharge,
4 kV in the case of contact discharge
EN 61000−4−3 RF interference (housing)
80 MHz  1000 MHz, 10 V/m 80 % AM (1 kHz)
EN 61000−4−4 Burst, severity: 3
EN 61000−4−5 Surge, severity 3 *
EN 61000−4−6 RF conducted
150 kHz  80 MHz, 10 V/m 80 % AM (1 kHz)
* Due to the high−energy single current pulses, a surge requires a suitable external connection with lightning
protection elements like for instance lightning conductors and overvoltage arresters.