Electrical installation
Important notes
4
EDKZS3X200 DE/EN/FR/ES/IT 1.1
27
H1_E_INST-Fi Verdraht_BF2
4 Electrical installation
Important notes
Danger!
The terminals also carry dangerous voltages even if the motor is stopped!
ƒ For this reason, check that the terminals are dead before you start working.
ƒ The sinusoidal filters from a rated current of 23.5 A may only be operated
with a mounted terminal cover. Otherwise, an electrical shock may occur
when touching the terminals.
Connection data
Sinusoidal filter
Terminal PE screw
Connection
cross-sections
Tightening torque ∅ Tightening torque
[mm
2
] [AWG] [Nm] [lb-in] [Nm] [lb-in]
EZS3-004A200
0.2 ... 6 24 ... 10 0.6 5.3
M4 2 17.7
EZS3-010A200
EZS3-017A200 0.5 ... 16 20 ... 6 1.5 13.3
EZS3-024A200
2.5 ... 25 10 ... 6 2 17.7
M5 3 26.5
EZS3-032A200
EZS3-037A200
EZS3-048A200
2.5 ... 35 12 ... 2
3 26.5
EZS3-061A200
EZS3-072A200
16 ... 50 1/0 ... 6
EZS3-090A200