Lenze i410 - Page 2

Lenze i410
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
GND
DO1
NO
COM
NC
U/I
V1-0
*P201.01
(configured AI1 as standard
setpoint)
*P400.02
Preset 01 (*P450.01)
*P100.00 output frequency
*P103.00 current actual value
Default seng
*P400.04
*P400.13
Start
Reset error
Mark direcon of rotaon
Acvate preset (bit 0)
Acvate preset (bit 1)
DO1 acvated at
Release brake
Relay acvated at
Ready for operaon
Analog input 1
Analog input 2
Analog output 1
10 VDC supply for potenometer
24 VDC, 100 mA supply, reference for digital inputs
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital output 1
GND for analog and digital signals
Relay NO contact
Relay centre contact
Relay NC contact
bit 1 bit 0
Preset frequency values
0
0
1
1
1
1
Preset 02 (*P450.02)
Preset 03 (*P450.03)
– Select standard setpoint source *P201.01.
– Run forwards/backwards [stac signals], start forwards/backwards [edge controlled]
– Enable quick stop *P400.03: Bring motor to a standsll in best me.
– Jog forwards *P400.10: Let motor rotate forwards with setpoint preset 05 (CW).
– Jog backwards *P400.11: Let motor rotate backwards with setpoint preset 06 (CCW).
Diagnoscs
P102.00 setpoint frequency [Hz]
P125.01 acve control source
P125.02 acve setpoint source
*P430.01 (0 ... 10 VDC signal)
*P430.02 — *P430.03
*P400.18
*P400.19
*P420.02
*P420.01
RDY
ERR
Meaning
off
off
No supply voltage.
2 Hz
off
Inverter inhibited.
Inverter inhibited, no DC-bus voltage.
Inverter inhibited, warning acve.
Inverter inhibited, error acve.
off
Inverter enabled and motor rotang or quick stop is acve.
Inverter enabled and motor rotang, warning signalled.
Inverter enabled, quick stop as response to fault acve.
Error message
Cause
Remedy
.2382
Ixt error
Reduce load, adapt ramps
.2383
Ixt warning
.3210
DC-bus overvoltage
Ramp me too short or motor is running in generator
mode
.3211
DC-bus overvoltage warning
.3220
DC-bus undervoltage
Check supply
.3221
DC-bus undervoltage warning
.3222
DC-bus voltage too low for switch-on
.6280
Trigger/funcon incorrectly connected.
In the case of flexible I/O configuraon *P200.01,
Inverter enable *P400.01 or Start *P400.02 must
have been assigned to an I/O. Do not use Start
forwards/backwards and Run forwards/backwards
at the same me.
.FF37
Automac start inhibited.
GND for analog and digital signals
EN-gb
range [Hz]:
config.: