Safety engineering
Safety functions
Safe stop 1
1
1.3
1.3.4
1.3-8
EDS94AYAD EN 2.2
1.3.4.2 Conditions
Condition for using the function:
ƒ The basic device must be equipped with a communication module
E94AYCPM (PROFIBUS-DP), SW version 0.9 and connected to the
PROFIBUS.
ƒ The basic device must receive PROFIBUS data telegrams from a master
controller.
Danger!
If the request for the safety function is cancelled, the drive will
restart automatically.
You must provide external measures which ensure that the drive
only restarts after a confirmation (EN 60204).
1.3.4.3 Settings
This function does not have any parameters to be set.
Permanently set parameters:
ƒ The stopping time amounts to t
s
=30s.
Tip!
In many applications the stopping time is < 30 s. Thus STO is
already activated and the SS1 function is stopped when ”0”
speed is reached.
Inordertodeterminethemaximumresponsetimeconsiderthe
stopping time (30 s).
This time can only be reduced by setting the STO function
through the safe control after the application-specific stopping
time.
1.3.4.4 Activation
How to activate the function:
ƒ A PROFIBUS data telegram with corresponding PROFIsafe contents is
transmitted to the basic device ( 1.3-12).