Fuse data (F1 ... F3)
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Cable installaon in compli-
ance with
  EN 60204-1
Installaon method   B2
Fuse    
  Characteriscs   gG/gL
 
Typ. rated current A 6 10
 
Max. rated current A 16 16
Semiconductor fuse    
  Characteriscs   gRL
 
Typ. rated current A 6 10
 
Max. rated current A 16 16
Circuit breaker    
  Characteriscs   C
 
Typ. rated current   6 10
 
Max. rated current A 16 16
 
•
Use of copper cables insulated with PVC
•
Conductor temperature < 70 °C, ambient temperature < 40 °C
•
No bundling of cables or wires, thee wires under load
Connecon for group drive according to EN 60204-1
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
Max. total rated mains currents at 40 °C
Cable installaon in compli-
ance with
  EN 60204-1
Laying system   B2
cable cross‐secon
mm
2
1.5 2.5
  (I
N1
 + L
N2
 + I
N3
+ I
Nn
) x 80% A 7.6 12.2
Fuse
  Characteriscs   gG/gL
 
Typ. rated current A --- ---
 
Max. rated current A 10 16
Circuit breaker
  Characteriscs   gRL
 
Typ. rated current A --- ---
 
Max. rated current A 10 16
 
•
Use of copper cables insulated with PVC
•
Conductor temperature < 70 °C, ambient temperature < 40 °C
•
No bundling of cables or wires, thee wires under load
Electrical installaon
Mains connecon
Connecon according to EN