Control logic
1.2 Inverter compressor starting
: Target Frequency calculation method
Step A = Step 1 Frequency (Min. frequency : 20~25Hz)
Step B = (Step A + Target Frequency) / 2
Step C = (Step B + Target Frequency) / 2
Step D = (Step C + Target Frequency) / 2
Step E = (Step D + Target Frequency) / 2
Target
frequency
(Hz)
Step A
Step B
Step C
Step D
Time (sec)
Step E