EasyManuals Logo

LG ARNU 483 NKA4 User Manual

LG ARNU 483 NKA4
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
STANDARD | 37
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED
Electrical Data
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of a fuse, use the circuit breaker.
Model Number
Voltage
Range
MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
SB Frames
ARNU053SBL4
187-253
0.2
15
0.16
60 208-230 1
21.0 21.0
ARNU073SBL4 0.2 0.16 21.0 21.0
ARNU093SBL4 0.2 0.16 21.0 21.0
ARNU123SBL4 0.2 0.16 21.0 21.0
ARNU153SBL4 0.2 0.16 21.0 21.0
SC Frames
ARNU183SCL4
187-253
0.36
15
0.29
60 208-230 1
39.5 39.5
ARNU243SCL4 0.36 0.29 39.5 39.5
Table 23: Standard Wall-Mounted Indoor Unit Electrical Data.