EasyManua.ls Logo

LG ARNU 763 B8A4 - General Data

LG ARNU 763 B8A4
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
STANDARD | 35
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED
General Data
Table 21: Standard Wall-Mounted (SB Frames) Indoor Unit General Data.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
with applicable and national code. Ensure the communication cable is properly grounded at the master
outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Model No. ARNU053SBL4 ARNU073SBL4 ARNU093SBL4 ARNU123SBL4 ARNU153SBL4
Cooling Mode Performance
Capacity (Btu/h)
5,500 7,500 9,600 12,300 15,400
Power Input
1
(W)
21 21 21 21 21
Heating Mode Performance
Capacity (Btu/h)
6,100 8,500 10,900 13,600 17,100
Power Input
1
(W)
21 21 21 21 21
Entering Mixed Air
Cooling Max (°F WB)
76 76 76 76 76
Heating Min (°F DB)
59 59 59 59 59
Unit Data
Refrigerant Type
2
R410A R410A R410A R410A R410A
Refrigerant Control
EEV EEV EEV EEV EEV
Sound Pressure
3
dB(A) (H/M/L)
32 / 30 / 28 32 / 30 / 28 34 / 31 / 30 40 / 34 / 31 42 / 40 / 34
Net Unit Weight (lbs.)
22 22 22 22 22
Shipping Weight (lbs.)
26 26 26 26 26
Communication Cable
4
(No. x AWG)
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type
Cross Flow Cross Flow Cross Flow Cross Flow Cross Flow
Quantity
1 1 1 1 1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
230 / 210 / 194 247 / 230 / 194 290 / 247 / 194 336 / 290 / 230 371 / 318 / 247
Piping
Liquid Line (in., O.D.)
1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare
Vapor Line (in., O.D.)
1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare
Condensate Line (in., I.D.)
1 1 1 1 1

Related product manuals