40 | HIGH STATIC
MULTI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
External Static Pressure Ranges
DUCTED HIGH STATIC
The table above shows the available E.S.P. range.
M2 Units, continued.
Model
Capacity
(MBh)
Mode Setting Value
Standard
ESP (in wg)
CFM Min. ESP (in wg)
Max. ESP (in
wg)
ARNU283M2A4 28.0
High
(Factory Set)
High 101
0.24
845
0.16 0.71Mid 95 676
Low 90 528
Standard
High 99
0.20
892
0.16 0.71Mid 94 770
Low 89 645
ARNU363M2A4 36.0
High
(Factory Set)
High 109
0.24
1031
0.16 0.71Mid 101 845
Low 95 676
Standard
High 105
0.20
1021
0.16 0.71Mid 97 844
Low 92 695
ARNU423M2A4 42.0
High
(Factory Set)
High 120
0.24
1260
0.16 0.71Mid 111 1076
Low 103 888
Standard
High 117
0.20
1262
0.16 0.71Mid 108 1087
Low 103 917
Table 26: M2 Unit External Static Pressure Ranges.