HIGH STATIC | 41
Ducted High Static
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 27: M3 Unit External Static Pressure Ranges.
DUCTED HIGH STATIC
External Static Pressure Ranges
M3 Units
Model Capacity (MBh) Mode
Setting
Value
Standard ESP
(in wg)
CFM
Min.
ESP (in wg)
Max.
ESP (in wg)
ARNU28GM3A4 28.0
High
(Factory Set)
High 86
0.23
1250
0.16 0.79Mid 82 1017
Low 78 837
Standard
High 83
0.19
1235
0.16 0.79Mid 79 1060
Low 75 915
ARNU36GM3A4 36.0
High
(Factory Set)
High 90
0.23
1449
0.16 0.79Mid 84 1191
Low 79 918
Standard
High 85
0.19
1327
0.16 0.79Mid 80 1097
Low 76 952
ARNU42GM3A4 42.0
High
(Factory Set)
High 90
0.23
1449
0.16 0.79Mid 84 1191
Low 79 918
Standard
High 85
0.19
1327
0.16 0.79Mid 80 1097
Low 76 952
ARNU48GM3A4 48.0
High
(Factory Set)
High 92
0.23
1482
0.16 0.79Mid 84 1191
Low 79 918
Standard
High 89
0.19
1457
0.16 0.79
Mid 82 1189
Low 76 952
ARNU54GM3A4 54.0
High
(Factory Set)
High 100
0.23
1744
0.16 0.79Mid 96 1614
Low 92 1482
Standard
High 97
0.19
1720
0.16 0.79Mid 92 1558
Low 88 1424
The table above shows the available E.S.P. range.