ELECTRICAL WIRING
ENGLISH
Display Title Cause of Error
Outdoor unit related error
2 6 1
Outdoor Unit Inverter Compressor
Start Failure
The First Start Failure by Outdoor Unit Inverter
Compressor Abnormality
2 9 1
Outdoor Unit Inverter Compressor
Over Current
Outdoor Unit Inverter Compressor Fault OR Drive
Fault
3 2 1
Outdoor Unit Inverter Compressor1
High Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge
Temperature
3 4 1 High Pressure of Outdoor Unit High Pressure of Outdoor Unit
3 5 1 Low Pressure of Outdoor Unit Low Pressure of Outdoor Unit
3 6 1
Outdoor Unit Low Compression Ratio
Limited
Outdoor Unit Low Compression Ratio Limited
4 0 1
Outdoor Unit Inverter Compressor CT
Sensor Fault
Outdoor Unit Inverter Compressor CT Sensor open
or short
4 1 1
Outdoor Unit Inverter Compressor1
Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
4 2 1
Outdoor Unit Low Pressure Sensor
Fault
Outdoor Unit Low Pressure Sensor open or short
4 3 1
Outdoor Unit High Pressure Sensor
Fault
Outdoor Unit High Pressure Sensor open or short
4 4 1
Outdoor Unit Air Temperature
Sensor Fault
Outdoor Unit Air Temperature Sensor open or short
4 5 1
Outdoor Unit Heat Exchanger
Temperature Sensor (Front side) Fault
Outdoor Unit Heat Exchanger Temperature
Sensor(Front side) open or short
4 6 1
Outdoor Unit Suction Temperature
Sensor Fault
Outdoor Unit Suction Temperature Sensor open or
short
5 0 1
Omitting connection of R, S, T power
of Outdoor Unit
Omitting connection of outdoor unit
5 1 1 Excessive capacity of indoor units
Excessive connection of indoor units compared to
capacity of Outdoor Unit
5 2 1
Communication error : inverter PCB
Main PCB
Failing to receive inverter signal at main PCB of
Outdoor Unit
5 3 1
Communication error : indoor unit
Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit.
5 7 1
Communication error : Main PCB
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Outdoor Unit
6 0 1
Inverter PCB EEPROM Error of
Master Outdoor Unit
Access Error of Inverter PCB of Outdoor Unit
6 2 1
Outdoor Unit Inverter Heatsink High
Temperature
System is turned off by Outdoor Unit Inverter
Heatsink High Temperature
6 5 1
Outdoor Unit Inverter Heatsink
Temperature Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor
open or short
1,MFL67798020, 2018. 4. 26. 7:06 Page 72
www.lgcomfortcooling.co.uk

Other manuals for LG ARUN050GSS0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG ARUN050GSS0 and is the answer not in the manual?

LG ARUN050GSS0 Specifications

General IconGeneral
BrandLG
ModelARUN050GSS0
CategoryAir Conditioner
LanguageEnglish

Related product manuals