40 Room Air Conditioner
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
Temperature range by COMP SPEC varies by 10°C.
Portection from overheating of power module
Portection from overheating of compressor
T off °C
T2 °C
Heat Sink Temp.
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
T = (T off - T on)
T1 = T on + T
T2 = T on + 2
*
T
D-Pipe Temp.
COMP Freq. Free Free
Fh min
OFFFc-1 Fc-1Fc-2 Fc-2
T = (T off - T2)/2
T1 = T2 - 2
*
T
T3 = T2 + T
T off °C
T2 °C
T3 °C
T1 °C
-13 °C
1 AS-W0964DH0/GH0 95 105
2 AS-W1264DH0/GH0 95 105
3 AS-W1865DH0 85 95
4 AS-W1224DH0 85 95
5 AS-W1424DH0 85 95
6 AS-W1825DH0 85 95
7 AS-W096E1G0 85 95
8 AS-W126E1G0 85 95
No. MODEL T on T off
1 AS-W0964DH0/GH0 95 105
2 AS-W1264DH0/GH0 95 105
3 AS-W1865DH0 98 108
4 AS-W1224DH0 95 105
5 AS-W1424DH0 95 105
6 AS-W1825DH0 98 108
7 AS-W096E1G0 100 110
8 AS-W126E1G0 100 110
No. MODEL T on T off
Operation

Other manuals for LG AS-W096E1G0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG AS-W096E1G0 and is the answer not in the manual?

LG AS-W096E1G0 Specifications

General IconGeneral
BrandLG
ModelAS-W096E1G0
CategoryAir Conditioner
LanguageEnglish

Related product manuals