WIRING CONNECTION
11
ENGLISH
Electrical Wiring
Perform the electrical wiring work according
to the electrical wiring connection.
- All wiring must comply with local require-
ments.
- Select a power source that is capable of sup-
plying the current required by the air condi-
tioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to ade-
quately disconnect all supply lines must be
fitted.
- Model of circuit breaker recommended by
authorized personnel only
Model Phase(ø) ELCB
AUUQ18GHT0/AUUW18GHT0
(ATUQ18GPLT0/ATUW18GPLT0)
(AVUQ18GJLT0/AVUW18GJLT0)
(ABUQ18GHLT0/ABUW18GHLT0)
1 25 A
AUUQ24GHT0/AUUW24GHT0
(ATUQ24GNLT0/ATUW24GNLT0)
(AVUQ24GKLT0/AVUW24GKLT0)
(ABUQ24GGLT0/ABUW24GGLT0)
1 25 A
AUUQ30GHT0/AUUW30GHT0
(ATUQ30GNLT0/ATUW30GNLT0)
(AVUQ30GKLT0/AVUW30GKLT0)
(ABUQ30GGLT0/ABUW30GGLT0)
1 30 A
AUUQ36GHT0/AUUW36GHT0
(ATUQ36GMLT0/ATUW36GMLT0)
(AVUQ36GLLT0/AVUW36GLLT0)
(ABUQ36GRLT0/ABUW36GRLT0)
1 30 A
AUUQ48GHT0/AUUW48GHT0
(ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ48GRLT0/ABUW48GRLT0)
1 40 A
AUUQ54GHT0/AUUW54GHT0
(ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ54GRLT0/ABUW54GRLT0)
1 40 A
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
1 40 A
ABUQ53GRLT0 1 40 A
ABUQ48LRLT0/ABUW48LRLT0/
ABUQ54LRLT0/ABUW54LRLT0
3 20 A
WIRING CONNECTION