FUNCTION
23
ENGLISH
Forced Cooling Operation
Adding the refrigerant in winter.
• When the green LED of PCB is on, com-
pressor is going to be off because of low
pressure.
• You should return the Dip Switch to oper-
ate normally after finishing the operation.
• Improper Pump down will lead to product
turn off along with LED (green &red) off
with in 20 minutes from the initial start.
Pump Down Dip S/W Setting
Power on
(Red LED On, Green LED Off)
WARNING
!
Setting Procedure
- Set the Dip Switch as follow after shutting the power source down.
- Reset the power.
- Red LED and Green LED of PCB lights during work. (The indoor unit is operated by force.)
- If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
- Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
AUUQ18GHT0/AUUW18GHT0
(ATUQ18GPLT0/ATUW18GPLT0)
(AVUQ18GJLT0/AVUW18GJLT0)
(ABUQ18GHLT0/ABUW18GHLT0)
AUUQ24GHT0/AUUW24GHT0
(ATUQ24GNLT0/ATUW24GNLT0)
(AVUQ24GKLT0/AVUW24GKLT0)
(ABUQ24GGLT0/ABUW24GGLT0)
AUUQ30GHT0/AUUW30GHT0
(ATUQ30GNLT0/ATUW30GNLT0)
(AVUQ30GKLT0/AVUW30GKLT0)
(ABUQ30GGLT0/ABUW30GGLT0)
AUUQ36GHT0/AUUW36GHT0
(ATUQ36GMLT0/ATUW36GMLT0)
(AVUQ36GLLT0/AVUW36GLLT0)
(ABUQ36GRLT0/ABUW36GRLT0)
AUUQ48GHT0/AUUW48GHT0
(ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ48GRLT0/ABUW48GRLT0)
AUUQ54GHT0/AUUW54GHT0
(ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
ABUW48LRLT0/ABUQ48LRLT0
ABUW54LRLT0/ABUQ54LRLT0