INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Unit : mm
Installation Places
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid
Standard
Max.
Standard
Max.
AUUQ18GHT0 18 kBtu/h Ø 12.7(1/2) Ø 6.35(1/4) 7.5 30 5 15 20
AUUW18GHT0 18 kBtu/h Ø 12.7(1/2) Ø 6.35(1/4) 7.5 50 5 30 20
AUUQ24GHT0
AUUW24GHT0
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40
AUUQ30GHT0
AUUW30GHT0
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40
AUUQ36GHT0
AUUW36GHT0
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40
AUUQ48GHT0
AUUW48GHT0
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8) 7.5 50 5 30 40
AUUQ54GHT0
AUUW54GHT0
AUUQ60GHT0
AUUW60GHT0
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8) 7.5 50 5 30 40
Free Joint Single Outdoor
Piping length and the elevation
INSTALLATION OF OUTDOOR UNIT