Part 2 Functions & Controls
4.2 High Ceiling operation
Function Code Thermistor setting
Select ceiling height value by pressing button. (01:Low,
02:Medium, 03:High, 04:Very high)
3
Press button to save.
4
5
If moving to ceiling height selection menu by pressing button,
it indicates as picture below.
2
If pressing button long for 3 seconds, it enters into
remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode.
Please press more than 3 seconds for sure.
1
Pressing button will exit settings mode.
After setup, it automatically gets out of setup mode if there is no button input
for 25 seconds.
When exiting without pressing set button, the manipulated value is not
reflected.
This function is to adjust FAN Airflow rate according to ceiling height (For ceiling type product)
• Ceiling height setting is available only for some products.
• Ceiling height of ʻVery highʼ function may not exist depending on the indoor unit.
• Refer to the product manual for more details.
<Ceiling Height Selection Table>
Ceiling Height Level Description
01 Low Decrease the indoor airflow rate 1 step from standard level
02 Medium Set the indoor airflow rate as standard level
03 High Increase indoor airflow rate 1 step from standard level
04 Very high Increase indoor airflow rate 2 steps from standard level