Part 4 Trouble Shooting
- 50 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
6.6 Troubleshooting Indoor Error
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10KΩ/ 5KΩ at 25°C, then sensor is normal.
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ’ Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ’ Repair or Change the PCB.
of each sensor.
Repair or Change the PCB.
of each sensor.
01
02
06
Indoor air sensor
Indoor inlet pipe sensor
Indoor outlet pipe sensor
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
Normal resistor : 10KΩ/ at 25˚C (Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Normal resistor : 5KΩ/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Normal resistor : 5KΩ/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Display
code
Title Cause of error Check point & Normal condition