Part 4 Trouble Shooting
- 52 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.
Check the wire
connection (Open,
Soldered poorly)
Drain pump check
Check drain tube
installation
Is it normal ?
Check the level of
water (Float moves top
position)
Is it normal ?
Check the wire
connection (Open,
Soldered poorly)
Is the float
switch clean ?
Yes
Yes
No
Check Drain Pump
Yes
No
Correct connection
Or re-soldering PCB
Is the resistance of
Drain Pump? Normal
( about 400Ω ) ?
Yes
No
Change the Drain Pump
Is the drain
pump clean ?
Yes
No
Clean drain pump
No
Clean float switch
Is the resistance of f
loat switch normal
(short) ?
Yes
No
Change the float switch
Is it normal ?
No
Correct connection
Or re-soldering PCB
Check Flow Chart
CN-Float
CN-D/Pump
04
Drain pump
/ Float switch
• Float switch open.
(Normal : short)
• Water over flow
• The connection of wire (Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
Display
code
Title Cause of error Check point & Normal condition