6. External Static Pressure & Air Flow
22
MULTI/SINGLE Indoor unit
Ceiling concealed duct - Middle static pressure
ABNW42GM2A0 [CM42 N24]
(Unit : CMM)
ABNW48GM3A0, ABNW60GM3A0
(Unit : CMM)
Note
The above table shows the correlation between the air rates and E.S.P.
Setting value
Static Pressure (mmAq(Pa))
5(49) 6(59) 8(78) 10(98) 12(118) 14(137) 15(147)
900 22.2
950 25.1 22.3
1000 28.0 25.4
1050 30.9 28.5 23.3
1100 33.8 31.6 26.8
1150 36.7 34.8 30.3 24.4
1200 39.7 37.9 33.8 28.3 23.5
1250 42.6 41.0 37.3 32.2 27.5
1300 44.1 40.8 36.1 31.6 26.1
1350 44.3 40.0 35.6 30.4 28.0
1400 43.9 39.7 34.6 32.4
1450 43.7 38.9 36.8
1500 43.1 41.2
1550 45.6
Setting value
Static Pressure (mmAq(Pa))
5(49) 6(59) 8(78) 10(98) 12(118) 14(137) 15(147)
700 25.1
750 29.5 26.1
800 34.0 30.8 25.9
850 38.4 35.4 30.6 23.2
900 42.9 40.1 35.2 28.1 21.0
950 47.3 44.8 39.9 33.1 26.3 19.5
1000 51.8 49.4 44.6 38.0 31.7 25.2 22.6
1050 56.2 54.1 49.2 43.0 37.1 31.0 28.5
1100 58.8 53.9 47.9 42.4 36.7 34.4
1150 58.6 52.9 47.8 42.5 40.3
1200 57.8 53.1 48.2 46.1
1210 54.2 49.4 47.3