1. Use the heat insulation material for the refriger-
ant piping which has an excellent heat-resis-
tance (over 120°C).
2. Precautions in high humidity circumstance:
This air conditioner has been tested according
to the "KS Standard Conditions with Mist" and
confirmed that there is not any default.
However, if it is operated for a long time in high
humid atmosphere (dew point temperature:
more than 23°C), water drops are liable to fall.
In this case, add heat insulation material
according to the following procedure:
Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to
20mm.
Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
In addition to the normal heat insulation
(thickness: more than 8mm) for refrigerant
piping (gas piping: thick piping) and drain pip-
ing, add further 10mm to 30mm thickness
material.
Indoor unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant piping
(3) Heat Insulation