Does the Operating LED of indoor unit blink
when Operation's ON?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 6
YES
NO
Is the connection of cable between indoor
and outdoor unit right?
Indoor Outdoor
1(Brown) 1(Brown)
2(Blue) 2(Blue)
3(Green/YL) 3(Green/YL)
4(Red) 4(Red)
NO
Is the voltage of CN-POWER , in out-
door PCB Ass'y about AC220V / 240V
when Operation's ON?
Check the Fuse of Outdoor PCB Ass'y.
NO
YES
Is the voltage of CN-AC CN-POWER(N) in
outdoor PCB Ass'y about AC220V / 240V?
Check the PTC and RY-PWR.
NO
YES
Is the Bridge Diode right?
Replace the Bridge Diode.
NO
YES
Replace the PCB Ass'y.
NO