-92-
The problem of missing the connector (SUB PCB ASSY)
Connectors
CN-UVW
CN-IPM
CN-GATE 1, 2
Condition
OPEN
OPEN
OPEN
Stop compressor.
Malfunctions inverter circuit.
Stop compressor and outdoor fan.
Malfunctions inverter circuit.
Stop compressor and outdoor fan.
Problem (error mode)
The problem of missing the connector (OUTDOOR MAIN PCB ASSY)
Connectors
CN-POWER
CN-AC
CN-DC
CN-IPM
CN-GND1, 2
CN-HEATER
CN-4WAY
CN-FAN 1, 2
CN-TH 1~6
CN-PWR
Condition
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN/SHORT
OPEN
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED02T blinks 5 times.
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED02T blinks 10 times.
Malfunctions inverter circuit.
Stop compressor and outdoor fan.
The operation LED02T blinks 9 times.
Malfunctions EMI / EMS
Malfunctions Sump Heater
Malfunctions 4-WAY valve.
Malfunctions fan.
The LED02T blinks twice.
The LED02T blinks 11 times.
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED02T blinks 8 times.
Problem (error mode)