2. Faults
2-1. Power
2-2.  Compressor
TROUBLE DIAGNOSIS
-44-
Problems Causes Checks Measures Remarks
No power on  - Power cord cut. - Check the voltage with tester. -Replace the components.
outlet. - Faulty connector insertion. - Check visually. -Reconnect the connecting parts.
- Faulty connection between plug - Check visually. - Reconnect the connecting parts.
and adapter.
Fuse blows out. - Short circuit by wrong connection. - Check the fuse with tester - Find and remove the cause of  - Replace with rated
- Low voltage products are  or visually. problem(ex. short, high voltage,  fuse after confirming
connected to high voltage. - Check the input volt are with tester low voltage).   its specification.
- Short circuit by insects. (between power cord and products). - Replace with rated fuse.
- Electricity leakage. - Check the resistance of power cord ■ If fuse blowns out
- High voltage. with testerf (if it is 0Ω, it is shorted). frequently, reconfirm
- Short circuit of components the cause and prevent.
(tracking due to moisture and dust
penetration).
Problems Causes Checks Measures Remarks
Compressor - Faulty PTC. - Check the resistance. - If resistance is infinite, replace it
does not  Vlaue:∞ is defective. with new one.
operate. - If it is not infinite, it is normal.
- Check other parts.
- Compressor is frozen. - If compressor assembly parts are  - During forced operation:
normal(capacitor, PTC, OLP),  - Operates: Check other parts.
apply power directly to the  - Not operate: Replace the frozen
compressor to force operation. compressor with new one, weld, 
evacuate, and recharge refrigerant.
OLP          It starts as soon as it is • Refer to weld repair procedures.
contacted.