5. Connecting Cables between Indoor Unit and Outdoor Unit
26
1) Connecting cables to the Indoor Unit
Connect the wires to the terminals on the control board individually according to the
outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as
those of indoor unit respectively
36K/42K/48K/60K Btu
18K/24K Btu
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm
2
cable(thinner cable) on the clamp and tighten it
with a plastic clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply
cord to the middle of live pin on the power plug should be over 1.8m.
POWER INPUT
Cooling & Heating type
Cooling only type
(380-415V3N~) (220-240V~)
Terminals on the indoor unit
12 453
Terminals on the outdoor unit
12 453
POWER
INPUT
POWER
INPUT
Terminals on the indoor unit
12 453
Terminals on the outdoor unit
123
Cooling only type
Cooling only type
Terminals on the indoor unit
1(L) 2(N) 4(N) 53(L)
Terminals on the outdoor unit
4(N) 5 63(L)
1(L) 2(N) 4(N) 5 6 7 83(L)
4(N) 5 6 73(L)
Terminals on the indoor unit
12 453
Cooling & Heating type
Terminals on the indoor unit
Terminals on the outdoor unit
Terminals on the outdoor unit
12 453
1(L) 2(N)
POWER INPUT
RS TN
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
The connecting cable connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
CAUTION
20m
m
G
N
/Y
L
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(18K/24K)
1.25mm
2
(30K/36K/42K/48K/60K)
20m
m
G
N
/Y
L
NORMAL CROSS-SECTIONAL AREA
Cooling only type
Cooling & Heating type
POWER
INPUT
Terminals on the indoor unit
123 564
Terminals on the outdoor unit
4(N) 5 6 73(L)
POWER
INPUT
Terminals on the indoor unit
123 564
Terminals on the outdoor unit
4(N) 5 6 73(L)
Capacity
18K BTU/h
24K BTU/h
30K BTU/h
36K BTU/h
42K BTU/h
48K BTU/h
60K BTU/h
1 Phase
2.5mm
2
2.5mm
2
3.3mm
2
5.5mm
2
8.5mm
2
3 Phase
-
-
-
2.5mm
2
-
3.5mm
2
3.5mm
2
Make sure that the screws of the terminal are free from looseness.
WARNING