Flared connection (Union)
Flared connection
(Service valve, Ball valve)
Use a seemliness tube
Factory charged
Indoor
Outdoor
REFRIGERANT PIPING
INSTALLATION OF OUT DOOR UNIT
Perform the work according to the Service
Manual or Installation Guide.
Select a location that satisfies the following
conditions. Install the unit firmly in place.
Select the following location
A place where the air conditioner can
get good ventilation.
A place where it shall not annoy the
neighbors.
A place where the unit shall be leveled
and that can support the weight of unit
and withstand its vibrations.
Keep a maintenance space
Above 70Cm
Above 30Cm
Outdoor unit
Above 30Cm Above 50Cm
Face of wall
Capacity Addition volume
18K BTU/h 30 g/m
24K BTU/h 30 g/m
36K BTU/h 40 g/m
48K BTU/h 40 g/m
60K BTU/h 50 g/m
Use two spanners when connect the
refrigerant pipe to the unit.
Make a bend with a radius as large as
possible.
After completing the piping connection,
execute vacuum drying for the connecting
piping and the indoor unit.
The vacuum drying must be carried out
using the service ports of both the liquid
and gas side valves.
When piping work is finished, check all
joints.
Add refrigerant if piping is over 7.5m.