Connecting Cables between Indoor Unit and Outdoor Unit
Installation Manual 23
ENGLISH
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
The connecting cable connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
CAUTION
20 mm
GN/YL
20 mm
GN/YL
NORMALCROSS-SECTIONA AREA 0.75 mm
2
(30 / 36 / 42 kBtu/h)
1.25 mm
2
(48 / 60 kBtu/h)
NORMAL CROSS-SECTIONAL AREA
Capacity
30 kBtu/h
36 kBtu/h
42 kBtu/h
48 kBtu/h
60 kBtu/h
1 Phase
5.5 mm
2
5.5 mm
2
3 Phase
-
2.5 mm
2
2.5 mm
2
3.5 mm
2
3.5 mm
2
-
-
-
20 mm
GN/YL
20 mm
GN/YL
1 Phase(1P) 3 Phase(3P4W) Cooling Only Heat Pump
CAUTION: Make sure that the screws of the terminal fixed tightly.