Refrigeration Cycle Diagram
- 14 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Heat Pump
• If 60K Model is installed at a distance of 15m, 525g of refrigerant should be added 
(15-7.5) x 70g = 525g
30k Btu/h
5/8" 3/8" 7.5 30 5 15 70
36k Btu/h
5/8" 3/8" 7.5 30 5 15 50
42k 
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
48k 
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
60k 
Btu
/h 3/4'' 3/8" 7.5 30 5 15 70
72k 
Btu
/h 1'' 1/2" 7.5 25 5 20 70
90k 
Btu
/h 9/8'' 5/8" 7.5 30 5 20 90
100k 
Btu
/h 9/8'' 5/8" 7.5 30 5 20 100
Capacity
Gas Liquid
Elevation B(m)
Piping Length
A(m)
* Additional
Refrigerant
(g/m)
Pipe Size (Diam-
eter: Ø)
inch
Standard
Standard
Max.
Max.
Model Name Orifice Number
LBNS3061BL/LBNS3062BL/LBNS3063BL/LBNS3064BL
63
LBNK3661BL 62
LBNK3663BL TBA
LBNK4261BL 74
LBNK4262BL/LBNK4263BL 72
LBNK4881BL 86
LBNK4882BL/LBNK4883BL 90
LBNM7280BL/LBNM7281BL 98
LBNM9080BL/LBNM9081BL 84
LBNM1080BL/LBNM1081BL 104
Orifice Number