Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
MultiFMAXInverterHeatPumpOutdoorUnit
DFSSBAJ001US012M18
Performance:
LMU540HV
Capacity(Btu/h) 54,000
CoolingPowerInput(kW)
5.10
HeatingPowerInput(kW)
5.34
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB Indoor: 70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB Outdoor: 47°FDB/43°FWB
Electrical:
PowerSupply(V¹/Hz/Ø) 208230/60/1
MOP(A)
40
MCA(A)
26.4
CoolingRatedAmps(A)
21
HeatingRatedAmps(A)
21
Compressor(A)
18.5
FanMotor
(
A
)
2.5
Piping:
RefrigerantCharge(lbs) 9.7
LiquidLine(in,OD)
3/8(1Each)
VaporLine(in,OD)
3/4(1Each)
MaxTotalPiping(ft)²
476
MaxElevationbetweenODUandIDU(ft)
98
MaxElevationbetweenIDUandIDU(ft)
49
ControlsFeatures:
•Autooperaon
•Autorestartoperaon
•Defrost/Deicing
•Inverter(variablespeed
compressor)
•NightQuietOperaon
•Lowambientoperaonto
14F(coolingmode)
•Restartdelay(3minutes)
•Selfdiagnosis
•Sostart
OperatingRange:
Cooling(°FDB) 14118
Heatin
g
(°FWB) 064
UnitData:
RefrigerantType R410A
RefrigerantControl
EEV
SoundPressure⁴Max(Cool/Heat)±3dB(A)
54/56
NetUnitWeight(lbs)
214
ShippingWeight(lbs)
236
HeatExchangerCoating
GoldFin™
MaxNumberofIndoorUnits
8
Compressor:
Quantity 1
Type
TwinRotaryInverter
Oil/Type
FVC68D
Fan:
Type Propeller
Quantity
2
FanMotor/Drive
BrushlessDigitallyControlled/Direct
AirflowRate(CFM)
2,119
StandardFeatures:
•LimitedSevenYearCompressorWarranty
•LimitedFiveYearFunctionalPartsWarranty
Notes:
1.Acceptableoperangvoltage:187V253V.
2.Pipinglengthsareequivalent.
3.AtleastoneBDUnitisrequiredforsystemoperaon;amaximumoftwocanbeinstalled
perODUwithuseofYbranchaccessory(PMBL5620).
4.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
5.Allcommu nicaoncabletobeminimum18AWG,2conductor,stranded,shieldedand
mustcomplywithapplicablelocalandnationalcode.
6.SeeEngineeringManualCapacityTablesforODUsensibleandlatentcapacies.
7.SeeEngineeringManualCombinaonTablesforallocaonofODUratedcapacitytoeach
connectedIDUwhenallare callingforfullcapacity.Allocationp ercentagesshouldbeapplied
toODUcapacityatdesignconditions.
8.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
9.Thisdataisrated0abovesealevel,with32.8ofrefrigerantlineanda0level
differencebetweenoutdoorandindoorunits.Allcapacitiesarenetwithacombinationratio
between95105%.
10.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
11.SeeEngineeringManualCapacityTablesforODUcapacityatdesigncondions.
MaxODUtoIDUPiping(ft) 230
PipingLength(noadd'lrefrigerant,ft)
147
CommunicationCable(No.xAWG)
4x16
MinNumberofIndoorUnits
2
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
O
p
tionalAccessories:
PI485IntegrationBoard‐PMNFP14A0
ACSmartII‐PQCSW320A1E
ACEz‐PQCSZ250S0
MOP‐MaximumOvercurrentProtection MCA‐MinimumCircuitAmpacity
ODU‐OutdoorUnit IDU‐IndoorUnit
AWG‐AmericanWireGage
PowerDistributionIndicator‐PQNUD1S00
2PortBDUnit‐PMBD3620
3PortBDUnit‐PMBD3630
4PortBDUnit‐PMBD3640
Page1of3
Re
q
uired³Accessories:
YBranch‐PMBL5620

Other manuals for LG LMU540HV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG LMU540HV and is the answer not in the manual?

LG LMU540HV Specifications

General IconGeneral
BrandLG
ModelLMU540HV
CategoryAir Conditioner
LanguageEnglish

Related product manuals