EasyManua.ls Logo

LG LS-L1261NL - Outdoor and Sub PCB Connector Issues

LG LS-L1261NL
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-66-
The problem of missing the connector (SUB PCB ASSY)
Connectors
CN-UVW
CN-AC
CN-DC
CN-IPM
Condition
OPEN
OPEN
OPEN
OPEN
Stop compressor.
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED blinks 5 times.
Malfunctions PFC & inverter circuit.
Stop compressor and outdoor fan.
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED blinks 5 times.
Problem (error mode)
The problem of missing the connector (OUTDOOR MAIN PCB ASSY)
Connectors
CN-POWER
CN-AC
CN-DC
CN-IPM
CN-GND1,2
CN-4WAY
CN-FAN
CN-OLP
CN-TH
CN-COMP
Condition
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN/SHORT
OPEN/SHORT
OPEN/SHORT
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED blinks 5 times.
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED blinks 5 times.
Malfunctions PFC & inverter circuit.
Stop compressor and outdoor fan.
Malfunctions EMI /EMS
Malfunctions 4-WAY valve.
Malfunctions fan.
Malfunctions Comp. Motor.
The operation LED blinks 4 times.
The LED01K blinks 4 times.
The operation LED blinks twice.
The LED01K blinks twice.
The LED01K blinks 10 times.
Continue Comp. operation.
(when the discharge pipe TH opens)
Stop Comp. operation
(when the discharge pipe TH shorts)
Malfunctions outdoor unit.
Stop compressor and outdoor fan.
The operation LED blinks 5 times.
Problem (error mode)

Related product manuals