84 | APPLICATION GUIDELINES
Single Zone Mega, Standard E󰀩ciency, and Mega 115V Wall Mounted Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Model Numbers
Refrigerant Piping Length (ft.)
16.4 24.6 32.8 41.0 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Mega, Standard Efficiency Models
LS090HEV2
(LSN090HEV2 / LSU090HEV2)
Additional
Refrigerant
Charge (oz.)
0 0 1.8 3.6 5.4 - - - - - - -
LS120HEV2
(LSN120HEV2 / LSU120HEV2)
0 0 1.8 3.6 5.4 - - - - - - -
LS180HEV2
(LSN180HEV2 / LSU180HEV2)
0 0 2.1 4.3 6.4 10.7 - - - - - -
LS240HEV2
(LSN240HEV2 / LSU240HEV2)
0 0 2.1 4.3 6.4 10.7 - - - - - -
LS090HFV3
(LSN090HFV3 / LSU090HFV3)
0 0 1.8 3.6 5.4
LS120HFV3
(LSN120HFV3 / LSU120HFV3)
0 0 1.8 3.6 5.4
LS180HFV3
(LSN180HFV3 / LSU180HFV3)
0 0 2.1 4.3 6.4 10.7
LS240HFV3
(LSN240HFV3 / LSU240HFV3)
0 0 2.1 4.3 6.4 10.7
Mega 115V Models
LS090HXV2
(LSN090HXV2 / LSU090HXV2)
Additional
Refrigerant
Charge (oz.)
0 0 1.8 3.6 5.4 - - - - - - -
LS120HXV2
(LSN120HXV2 / LSU120HXV2)
0 0 1.8 3.6 5.4 - - - - - - -
Table 56: Single Zone Mega, Standard Efciency, and Mega 115V Piping System Additional Refrigerant Charge.
Capacity is based on standard length.
Equivalent Pipe Length = Actual Pipe Length + Number of Bends x 0.3.
Additional Refrigerant Charge Calculation : X (g) = [ (Refrigerant Pipe Length) - (No Charge Pipe Length) ] × (Additional Refrigerant).
There is no need to add refrigerant if equivalent pipe is less than the “piping length with no additional refrigerant” in the table above.
REFRIGERANT PIPING DESIGN