8. Defrost Control
• Defrost operation is controlled by timer and sensing the outdoor piping temperature.
• The defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting
of heating operation.
• Defrost ends after 9 minutes 30 seconds passed from starting of defrost operation or when the outdoor pipe
temperature rises over 12°C even if before 12 minutes.
9. Self-Diagnosis Function
• 'CH' will flash in the remote controller display when a problem occurs. Then please contact your dealer.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CH' won't be displayed in the remote controller.
Remote controller LCD Accident Point
CH 01 Indoor temperature thermistor error
CH 02 Indoor piping thermistor error
CH 03 Indoor/Outdoor unit communication error
CH 04 Water level float switch error