–32–
Install certainly the decorative panel.
Cool air leakage causes sweating. Water drops fall.
• Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent rever-
sal flow.
• During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the
indoor unit is 32mm.
• Be sure to execute heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exteri-
or and leave it provisionally until the test
comes to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for nor-
mal operating and noise when electrical
wiring is complete.
• When the test is complete, connect the
flexible drain hose to the drain port on
the indoor unit.
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
8. INDOOR UNIT DRAIN PIPING
Drain test