Method to connect power cord
Release two screws and then open the
cover of the control box.
•
With reference to the below wiring diagram, accu-
rately connect the main power cords into the termi-
nal block.
After inserting the power cord into the bushing, fully insert it into the termi-
nal block for connection.
• Fix the power cords with the clamp.
• Make sure that the power cords may not be removed by pulling them.
Wiring specifications
Wiring specifications
Sheathed wire (should be complied with 60245 IEC 53 standard)
Size 0.75 - 1.25 mm
2
Length MAX. 100 m
External contact specifications Normally closed contact (Current tolerance 10 mA - 0.5 A)
Indoor unit ground wires are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).