APPLICATION GUIDELINES | 67
Application Guidelines
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Formula
Total Louver Dimension (Excluding Frame) (A) = 3.9 feet x 6.2 feet = 24.2 ft.
2
Area Blocked by Outdoor Unit (Discharge) (B) = 2.6 feet x 2.8 feet = 7.41 ft.
2
Inlet Louver Dimension (A - B) = 16.8 ft.
2
Equivalent Inlet Dimension (Open Rate 80%) = 16.8 ft.
2
x 0.8 = 13.44 ft.
2
Equivalent Inlet Airflow = 13.44 ft.
2
x 8.2 ft./s x 60 sec./min. = 6,612 ft.
3
/min.
Equivalent Inlet Airflow / Discharge Airflow = 6,612 ft.
3
/min. / 2,119 ft.
3
/min. = 312% (Within Allowable Limits)
Confirming Air Flow Rate / Total Opening Rate
• Example: LSU180HSV5.
Discharge Airflow Rate: 2,119 ft.
3
/min.
Velocity of Outlet Air: 16.4 ft./s
Velocity of Inlet Air: 8.2 ft./s
Open Rate = 80% or More
Inlet airflow must match or exceed discharge airflow.
Separate inlet airflow from discharge airflow to
prevent recirculation.
Figure 37: Open Rate by Louver Radian Formula.
Open Rate = Effective Face Area (Af)
Total Face Area (A)
Side View
ho = h * COS
Total Area (A) = H * W
Number of Open Spaces (N) = (Number of Louvers - 1)
Effective Area (Af) = ho * W * N
Louver Open Rate (n) = Af / A
Af = A * n
Effective Cross Section Area
ho
h
W
Front View
H

Open Rate by Louver Radian
Figure 38: Example of Installing Outdoor Unit Indoors.
PLACEMENT CONSIDERATIONS
,QVWDOOLQJ2XWGRRU8QLWV,QGRRUV
55-1/8
47-1/4
34-1/4
74-13/16
31-1/2
Unit: Inch
Louver Dimensions Air Guide Duct on
Outdoor Unit
Outdoor Unit
Dimensions